High Power Density Flexible Expansion 100kw 250kw 500kw 1mw PCS Power Conversion System With Built In Isolation Transformer
Overview
Inquiry
Related Products



Model |
0030TS |
0050TS |
0100TS |
0150TS |
0250TS |
0500TS |
||||||
DC(battery) |
||||||||||||
Voltage range (V) |
250~850 |
320~850 |
420~850 |
420~850 |
420~850 |
500~850 |
||||||
Max. Current (A) |
137 |
178 |
270 |
405 |
673 |
1,128 |
||||||
AC(on-grid) |
||||||||||||
Max output power(kVA) |
33 |
55 |
110 |
165 |
275 |
550 |
||||||
Rate output power(kW) |
30 |
50 |
100 |
150 |
250 |
500 |
||||||
Rated voltage(V) |
400 |
|||||||||||
Voltage range(V) |
320~460 |
|||||||||||
Rated current(A) |
43 |
72 |
144 |
216 |
361 |
722 |
||||||
Max. output current(A) |
48 |
80 |
59 |
238 |
397 |
794 |
||||||
Rated frequency (Hz) |
50/60 |
|||||||||||
AC connection |
3W+N+PE |
|||||||||||
General data |
||||||||||||
Max.efficiency |
96.3% |
96.5% |
97.1% |
97.1% |
97.3% |
97.5% |
||||||
Ingress protection |
IP21 |
|||||||||||
Noise emission (dB) |
<70 |
|||||||||||
Cooling |
Forced air |
|||||||||||
Dimension W*D*H (mm) |
800*800*1,900 |
800*800*1,900 |
800*800*1,900 |
800*800*1,900 |
1,200*800*2,050 |
1,600*1,050*2,050 |
||||||
Net Weight(kg) |
621 |
712 |
936 |
1,057 |
1,582 |
2,665 |
||||||
Transformer ratio |
100/400 |
200/400 |
270/400 |
270/400 |
270/400 |
315/400 |
||||||
Self-consumption (W) |
<100 |
<208 |
||||||||||
On/ Off grid switching |
Automatic |
|||||||||||
Display and communication |
||||||||||||
Display |
LCD touch-screen |
|||||||||||
BMS communication |
RS485, CAN |
|||||||||||
EMS communication |
RS485, TCP/IP |
|||||||||||
Certificates |
IEC/EN62109-1/-2, IEC/EN 62477-1 , IEC/EN 61000-6-2, IEC/EN 61000-6-4, CGC |